Smoke Fans

The NOVENCO® smoke fans are for installation and operation in environments and systems which require normal temperature ventilation and which must have a capacity for operation in high temperature conditions to protect lives and assets. Typical application of smoke fans is as exhaust fans in the event of fires in buildings, stairwells, car parks, tunnels etc.

The fans in the NOVENCO smoke fan ranges are compact, efficient, robust and reliable and include both the renowned NOVENCO NovAxTM as well as the latest addition, the extremely efficient NOVENCO ZerAx® , axial flow fans. Both fan ranges enjoy strong market positions in terms of quality and performance.

All NOVENCO smoke fans are approved in accordance to EU regulations. Furthermore, the ZerAx fans are also approved for operation as smoke fans with frequency converters (VSDs).

The range of sizes and capacities cover low to medium pressure systems for normal ventilation and for removal and transport of air within smoke-filled high temperature environments.

 

 

Smoke Fans ZerAx AZL
The ZerAx® HT AZL smoke exhaust fans with integrated inlet cones are for conventional ventilation and operation during fires in car parks, tunnels and all types of buildings. The design is tested and approved to meet requirements for smoke exhaust in combination with frequency converters.

Product facts
• Integrated inlet cone
• Outlet duct installation
• 13 sizes with impeller diameters from Ø250 to Ø1000 mm
• Two hub sizes – Ø160 or Ø350 mm
• Fan casing thicknesses of 2 or 3 mm
• Airflow rates
   • 0.1 to 33 m3/s
   • 350 to 119.000 m3/h
• Pressures up to 3100 Pa
• Efficiencies up to 89%
• Adjustable blade angles
• F300 certified according EN 12101 part 3 in combination with variable speed drive (VSD)
• Air over motor (cooling)
• Fan casing materials
   • for light motors: pre-coated sheet metal with AZ185 or ZM310 coating according to EN10346:2015
   • for heavy motors: hot-dip galvanised steel
• Corrosion categories
   • Standard: C3
   • Optional: C4 or C5
• Impeller, guide vanes and motor mount of aluminium
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Optional executions
   • Standard temperature
• Product configuration with AirBox™

 

Smoke Fans ZerAx AZN
The ZerAx® HT AZL smoke exhaust fans with integrated inlet cones are for conventional ventilation and operation during fires in car parks, tunnels and all types of buildings. The design is tested and approved to meet requirements for smoke exhaust in combination with frequency converters.

Product facts
• Integrated inlet cone
• Outlet duct installation
• 13 sizes with impeller diameters from Ø250 to Ø1000 mm
• Two hub sizes – Ø160 or Ø350 mm
• Fan casing thicknesses of 2 or 3 mm
• Airflow rates
   • 0.1 to 33 m3/s
   • 350 to 119.000 m3/h
• Pressures up to 3100 Pa
• Efficiencies up to 89%
• Adjustable blade angles
• F300 certified according EN 12101 part 3 in combination with variable speed drive (VSD)
• Air over motor (cooling)
• Fan casing materials
   • for light motors: pre-coated sheet metal with AZ185 or ZM310 coating according to EN10346:2015
   • for heavy motors: hot-dip galvanised steel
• Corrosion categories
   • Standard: C3
   • Optional: C4 or C5
• Impeller, guide vanes and motor mount of aluminium
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Optional executions
   • Standard temperature
• Product configuration with AirBox™

 

Smoke Fans NovAx ACN
The NovAx ACN smoke exhaust fans are for conventional operation and operation during fires in carparks, commercial and industrial buildings, tunnels and more. The design is tested and approved to meet requirements for smoke exhaust.

Product facts
• For duct installation
• 12 sizes with impeller diameters from Ø400 to Ø1600 mm
• Six hub sizes from Ø230 to Ø578 mm
• Fan casing thicknesses of 2 or 4 mm
• Airflow rates from 0.2 to 65 m3/s
• Pressures up to 1800 Pa
• Efficiencies up to 83%
• Adjustable blade angles
• F200, F300 and F400 certified according EN 12101 part 3
• Air over motor (cooling)
• Fan casing and hub of galvanised steel
• Impeller blades of aluminium
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Also available in standard temperature execution
• Product configuration with AirBox™

 

Smoke Fans NovAx ACN Standard
The NovAx ACN smoke exhaust fans are for conventional operation and operation during fires in carparks, commercial and industrial buildings, tunnels and more. The design is tested and approved to meet requirements for smoke exhaust.
 
Product facts
• For duct installation
• 26 predefined combinations of fan and hub sizes, airflows and pressures
• Impeller diameters from Ø500 to Ø1400 mm
• Airflow rates from 2.8 to 27.8 m3/s
• Total pressures up to 1300 Pa
• Efficiencies up to 83%
• F300 certified according EN 12101 part 3
• Air over motor (cooling)
• Fan casing and hub of galvanised steel
• Impeller blades of aluminium
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Product configuration with AirBox™

 

FacebookLinkedIn Smoke Fans NovAx ACP ACG
The NovAx ACP-ACG smoke exhaust fans are for conventional, industrial and marine environments and suitable for operation during fires in carparks, commercial and industrial buildings, tunnels and more. The design is tested and approved to meet requirements for smoke exhaust.

The ACG fans are fitted with an additional guide vane arrangement to increase fan efficiency.

Product facts
• Mounting
    • ACP: For wall or bulkhead
    • ACG: For duct ends
• 12 sizes from Ø400 to Ø1600 mm
• Seven hub sizes from Ø160 to Ø578 mm
• Fan casing thicknesses of 2.5, 3 or 4 mm depending on size
• Airflow rates from 0.2 to 65 m3/s
• Pressures up to 2000 Pa
• Efficiencies up to 83%
• Adjustable blade angles
• F200, F300 and F400 approved for smoke extract
• Integrated inlet cone
• ACG: Additional guide vane arrangement
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Also available in standard temperature execution
• Product configuration with AirBox™

 

Smoke Fans NovAx ARN
The NovAx ARN smoke exhaust fans are fully reversible and for conventional operation and operation during fires in carparks, commercial and industrial buildings, tunnels and more. The guide vanes are straight, which is in contrast to other NovAx fans, and give the fully reversible feature. The design is tested and approved to meet requirements for smoke exhaust.

Product facts
• For duct installation
• Six sizes with impeller diameters from Ø900 to Ø1600 mm
• Two hub sizes, Ø403 or Ø578 mm
• Fan casing thicknesses of 2 or 4 mm
• Airflow rates
    • 5 to 50 m3/s
    • 18.000 to 180.000 m3/h
• Pressures up to 1200 Pa
• Efficiencies up to 75%
• 100% reversible
• Adjustable blade angles
• Air over motor (cooling)
• F200, F300 and F400 certified according EN 12101 part 3
• Fan casing and hub of galvanised steel
• Impeller blades of aluminium; guide vanes, hubs and • motor mount of galvanised steel
• Accessories for mounting, connection, sound attenuation, safety and regulation
• Also available in standard temperature execution

Phone +86 411 3954 9055